Jump to content

Regupol Vibration Isolation

The building authority approved REGUPOL vibration range offers a portfolio of eight product types which can be used in the wide load range between 0.002 N/mm² and 1.5 N/mm². This creates many possibilities to implement an isolation concept for projects in the field of building services and HVAC equipment, machines, pools and gyms, as well as vibration protection for buildings, especially those in close proximity to rail infrastructure. Regupol® vibration is a rubber-polyurethane-composite for vibration isolation. It can be used in single or multiple layers to achieve natural frequencies of down to 10 Hz, depending on load and material thickness.

Product Characteristics

Continuous static load
0.80 N/mm²

Peak loads (rare, short-term loads)
1.00 N/mm²

Standard forms of delivery, ex warehouse

Rolls
Thickness: 10 mm
Length: 8,000 mm, special length available
Width: 1,250 mm

Stripping/Plates
On request: Die-cutting, water-jet cutting, self-adhesive versions possible

 

Technical Specifications

regupol-vibration-800-specifications.xlsx

Regupol Vibration 800

Physical property Norm Result Comment
Static modulus of elasticity Based on EN 826 1.2 - 2.9 N/mm2 Tangential modulus, see figure “modulus of elasticity”
Dynamic modulus of elasticity Based on DIN 53513 3.6 - 18.2 N/mm2 Depending on frequency, load and thickness, see figure “dynamic stiffness“
Mechanical loss factor DIN 53513 0.18 Load-, amplitude- and frequency-dependent
Compression set Based on DIN EN ISO 1856 3.7 % Measured 30 minutes after decompression with 50 % deformation / 23 °C after 72 hrs
Tensile strength Based on DIN EN ISO 1798 0.9 N/mm2
Elongation at break Based on DIN EN ISO 1798 70%
Tear resistance Based on DIN ISO 34-1 8.0 N/mm
Fire behaviour DIN 4102 B2
DIN EN 13501-1 E
Sliding friction REGUPOL-laboratory 0.7 Steel (dry)
REGUPOL-laboratory 0.8 Concrete (dry)
Compression hardness Based on DIN EN ISO 3386-2 545 kPa Compressive stress at 25 % deformation test specimen h = 60 mm
Rebound elasticity Based on DIN EN ISO 8307 30% dependent on thickness, test specimen h = 60 mm
Force reduction DIN EN 14904 61% dependent on thickness, test specimen h = 60 mm
Ozone resistance DIN EN ISO 17025 Cracking stage 0  

Interested in Regupol Vibration 800?

Feel free to contact us for more information