Regupol Vibration Isolation
The building authority approved REGUPOL vibration range offers a portfolio of eight product types which can be used in the wide load range between 0.002 N/mm² and 1.5 N/mm². This creates many possibilities to implement an isolation concept for projects in the field of building services and HVAC equipment, machines, pools and gyms, as well as vibration protection for buildings, especially those in close proximity to rail infrastructure.
Regupol® vibration is a rubber-polyurethane-composite for vibration isolation. It can be used in single or multiple layers to achieve natural frequencies of down to 10 Hz, depending on load and material thickness.
Variations
Product Characteristics
Continuous static load
1.50 N/mm²
Peak loads (rare, short-term loads)
1.75 N/mm²
Standard forms of delivery, ex warehouse
Rolls
Thickness: 10 mm
Length: 8,000 mm, special length available
Width: 1,250 mm
Stripping/Plates
On request: Die-cutting, water-jet cutting, self-adhesive versions possible
Technical Specifications
regupol-vibration-1000-specifications.xlsx
Regupol Vibration 1000
Physical property | Norm | Result | Comment |
Static modulus of elasticity | Based on EN 826 | 4.0 - 11.0 N/mm2 | Tangential modulus, see figure “modulus of elasticity” |
Dynamic modulus of elasticity | Based on DIN 53513 | 15.0 - 45.0 N/mm2 | Depending on frequency, load and thickness, see figure “dynamic stiffness“ |
Mechanical loss factor | DIN 53513 | 0.16 | Load-, amplitude- and frequency-dependent |
Compression set | Based on DIN EN ISO 1856 | 4.9 % | Measured 30 minutes after decompression with 50 % deformation / 23 °C after 72 hrs |
Tensile strength | Based on DIN EN ISO 1798 | 2.3 N/mm2 | |
Elongation at break | Based on DIN EN ISO 1798 | 110% | |
Tear resistance | Based on DIN ISO 34-1 | 15.0 N/mm | |
Fire behaviour | DIN 4102 | B2 | Narmal flammability |
DIN EN 13501-1 | E | ||
Sliding friction | REGUPOL-laboratory | 0.6 | Steel (dry) |
REGUPOL-laboratory | 0.7 | Concrete (dry) | |
Compression hardness | Based on DIN EN ISO 3386-2 | 1650 kPa | Compressive stress at 25 % deformation test specimen h = 60 mm |
Rebound elasticity | Based on DIN EN ISO 8307 | 37% | dependent on thickness, test specimen h = 60 mm |
Force reduction | DIN EN 14904 | 45% | dependent on thickness, test specimen h = 60 mm |
Ozone resistance | DIN EN ISO 17025 | Cracking stage 0 |
Contact Us
Interested in Regupol Vibration 1000?